The device can only be reset by a hardware reset on the device itself.
Note |
|
|---|---|
|
If you reset the device to factory settings, the entire module configuration including the owner of this configuration will be deleted. |
|
Procedure
-
Move the configuration switch to the Rst position, hold it there and press the reset button at the same time.
The reset button can be pressed with a suitable object (e. g. ballpoint pen).
After a reset, the device restarts and the status indicators flash.
Device and module configurationare reset.
-
You can release both the reset button and the configuration switch again.
The configuration switch returns to the Static position.
-
Set the configuration switch for user-defined IP settings to the Cfg switch position.
Device configuration after reset
|
Owner: |
none |
|
Device name: |
ibaW-xxxxxx xxxxxx = 6-digit serial number, e. g. ibaW-000046 The serial number can be found on the type label |
|
IP address: |
192.168.1.1 |
|
Subnet mask: |
255.255.255.0 |
|
Gateway: |
0.0.0.0 |
|
DHCP: |
no |