Bus interface (K-bus)

Number

1

Design

terminal bus

Data volume

up to 2048 bytes

Number of bus terminals

up to 64, with terminal bus extension 250

Sampling rate

according to bus cycle time, system-dependent minimum 1 ms;

The update time of the signals may vary due to terminal-specific properties.

Connection technology

6 sliding contacts, according to WAGO I/O system 750, incl. power supply

ibaNet interface

Number

2; switched

Design

copper

ibaNet protocol

ibaNet-E

Number of ibaPDA connections

1

Data volume

min. 320 Bytes at max. ibaNet-E sampling rate (1 kHz), depending on ibaNet-E sampling rate

Sampling rate

1 Hz - 1 kHz, freely adjustable

Connection technology

2 RJ45 sockets (10/100 Mbit/s)