ibaNet
|
Number |
1 (e. g. for the connection to ibaPDA) |
|
|
ibaNet protocol |
32Mbit Flex (bidirectional) |
|
|
Connector type |
2 ST connectors for RX and TX; iba recommends the use of FO with multimode fibers of type 50/125 μm or 62.5/125 μm; For information on cable length, see Example for FO budget calculation |
|
|
Transmitting interface (TX) |
||
|
Output power |
50/125 µm FO cable: |
-19.8 dBm to -12.8 dBm |
|
62.5/125 µm FO cable: |
-16 dBm to -9 dBm |
|
|
100/140 µm FO cable: |
-12.5 dBm to -5.5 dBm |
|
|
200 µm FO cable: |
-8.5 dBm to -1.5 dBm |
|
|
Temperature range |
-40 °F to 185 °F (-40 °C to 85 °C) |
|
|
Light wavelength |
850 nm |
|
|
Laser class |
Class 1 |
|
|
Receiving interface (RX) |
||
|
Receiving sensibility1 |
100/140 µm FO cable: |
-33.2 dBm to -26.7 dBm |
|
Temperature range |
-40 °F to 185 °F (-40 °C to 85 °C) |
|
Other interfaces
|
Ethernet |
10/100 Mbit/s |
|
USB |
2x host, 1x device for service purposes |