Voltage dip

Signal

Description

Dip event (digital)

Active, if the half period RMS value of at least one phase is lower than the limit.

Dip event Start

Current_time – start_time, in seconds, while the event is running.

Dip event Duration

Previous duration of events, in seconds, while the event is running.

Dip event Min

Minimum half period RMS value, in V, while the event is running.

The limit is increased by the hysteresis, if the event is active.

The limit is calculated as percentage value of the nominal voltage or as percentage value of the floating reference value.

Note: this value is calculated for each phase separately.

Voltage swell

Signal

Description

Swell event (digital)

Active, if the half period RMS value of at least one phase is higher than the limit.

Swell event Start

Current _time – start_time, in seconds, while the event is running.

Swell event Duration

Previous duration of events, in seconds, while the event is running.

Swell event Max

Maximum half period RMS value, in V, while the event is running.

The limit is reduced by the hysteresis, if the event is active.

The limit is calculated as percentage value of the nominal voltage or as percentage value of the floating reference value.

Note: this value is calculated for each phase separately.

Voltage interruption

Signal

Description

Interruption event (digital)

Active, if the half period RMS value of all phases of a supply voltage grid is lower than the limit.

Interruption event Start

Current_time – start_time, in seconds, while the event is running.

Interruption event Duration

Previous duration of events, in seconds, while the event is running.

Interruption event Min

Minimum half period RMS value, in V, while the event is running.

The limit is increased by the hysteresis, if the event is active.

The limit is calculated as percentage value of the nominal voltage.

Mains signalling

Signal

Description

Mains signalling event (digital)

Active, if the RMS value of the mains signalling voltage on at least one phase is higher than the limit set.

Mains signalling event Start

Current_time – start_time, in seconds, while the event is running.

Mains signalling event Duration

Previous duration of events, in seconds, while the event is running.

Mains signalling event Max

Maximum RMS value of the mains signalling voltage, in V, while the event is running.

Rapid voltage change (RVC)

Signal

Description

Rapid voltage change (digital)

Active, if the half period RMS value of at least one phase is beyond the area Floating_average – limit or Floating_average + limit.

RVC event Start

Current_time – start_time in seconds.

RVC event Duration

Duration of the event in seconds.

RVC event Delta Umax

Maximum deviation from the floating average at the starting point of the event, in V.

RVC event Delta Uss

Change in the floating average between start and 1 second after the event, in V.

The floating average is the arithmetic average of the last 100 (at 50 Hz) or 120 (at 60 Hz) half period RMS values. This corresponds to the average of the last second.

The limit is reduced by the hysteresis while the event is active.