For ibaBM-DP, specify an iba-PROFIBUS slave for each module.
Use the GSD file ibaDPMSi.gsd (version V2.2 and higher).
Note |
|
|---|---|
|
You find the GSD file
|
|
Note |
|
|---|---|
|
The slots have to be created without gaps and with consecutive address range. |
|
S7-CPUs of newer type 1 provide consistent slots with a max. of 128 Bytes. Use the elements "S7-Req block consistent Slot 0 / Slot 1".
For S7-CPUs and for CP443-5 of older types, you cannot use long consistent slots. Use the elements "S7-Req unit consistent Slot 0 / Slot 1".