You find the description of all settings that are identical for all Request-S7 modules in chapter General module settings .

The ibaBM-DPM-S modules all have the following common specific settings options.

PROFIBUS

Bus number

0 = connector X40 top, 1 = connector X41 bottom

Slave No.

PROFIBUS slave address assigned to the module.

Connection

Auto enable/disable

If TRUE, the acquisition is started, even if no connection can be established to the S7-CPU. The module is disabled. During the acquisition, ibaPDA tries to reconnect to the S7-CPU. When it succeeds, the acquisition is restarted with this module enabled. In case of FALSE, the acquisition is not started, if a connection to the configured S7-CPU cannot be established.