Description of formal parameters

Name

Type

Data Type

Description

adrSlot0 … adrSlot5

IN

VARIANT

Starting address of the output range

reset_com

IN

BOOL

FALSE: No reset (default) TRUE: Reset of the communication connection

DB_PDA

INOUT

UDT

DB for the ibaPDA communication interface ibaREQ_DB_PDA

state

OUT

STRING[16]

Block status

statusSlot0 … statusSlot5

OUT

WORD

Internal error code

Detailed description

adrSlotx

Starting address of the slot used in the output range of the process image.

You can configure up to 6 slots. For data consistency, the length of slots 0…4 must be a multiple of 8. If a slot is not to be used, configure any symbol that does not refer to an output address.

reset_com

Used for manually resetting the communication connection.

DB_PDA

Pointer to the communication data range. This range is used for the data exchange with ibaPDA. For all related Request blocks, configure the identical DB.

statusSlotx

Internal error code of the block related to the slot with the same number. If no error is present, the value 0 is output.

Error codes

Hexadecimal value errorStatus

Description

01x8001

no connection to PN device or error (error GET_DIAG)

01x8010

internal error (error IO2MOD)

01x8011

internal error (error LOG2GEO)

01x8012

internal error (error LOG2GEO)

01x8013

internal error (error LOG2GEO)

01x8014

internal error (error RD_ADDR)

01x8020

slot size not a multiple of 8 and not the last slot

01x8401

DPWR_DAT failed invalid hw-id

01x8402