The following tables provide information on the cycle time extension you can expect for ibaPDA in conjunction with L2B-Request depending on the S7-CPU type.

Test series with up to 256 analog signals and 256 digital signals (8 slaves) were used to obtain the time values. The measurement values were determined in a test environment and only serve as reference points. The values may deviate in other system environments.

S7-CPUs with integrated DP interface

S7-CPU type

Max. cycle time extension per slave(32 analog signals + 32 digital signals)

316- 2AG00

13 ms

314- 6CF00

8.63 ms

315- 2AG10

6.88 ms

317- 2EJ10

0.875 ms

317- 6FF00

1.125 ms

318- 2AG00

0.75 ms

416- 2XK00

1.25 ms

413- 2XG02

2.625 ms

414- 2XG03

0.875 ms

416- 2XK04

0.375 ms

S7-CPUs with external DP interface (CP)

S7-CPU type/ CP

Max. cycle time extension per slave(32 analog signals + 32 digital signals)

CPU315 with CP342- 5

6.0 ms

CPU318 with CP342- 5

0.75 ms

CPU416 with CP443- 5

0.625 ms