Number |
4 |
|
Design |
1 root with 4 outputs |
|
Resolution |
16 bit |
|
Filter |
R/C low-pass 40 kHz, permanent |
|
Output signal range |
-10 V … +10 V |
|
Load |
≥ 1 kΩ |
|
R/C low-pass 40 kHz, permanent |
max. 40 kHz1, freely adjustable |
|
Delay |
8 μs + 12 µs (12µs = settling time until 90 % of the output value is reached) |
|
Accuracy |
< 0.1 % of total measuring range |
|
Electrical isolation |
|
|
Root-root |
1.5 kV AC |
|
Root - housing/power supply |
1.5 kV AC |
|
Connection type |
1x 10-pin multi-pin connector screw-type terminal (0.14 mm2 to 1.5 mm2), screw connection, included in delivery |
|
Protective functions |
|
|
Safe state |
channel root switched off |
|
Current limitation |
short circuit protection |
|
Hardware error (e. g. overtemperature) |
The root switches to „safe state“, when connection is incorrect (resettable via software) |