Number |
3 |
||
|
Version |
Galvanically isolated, single ended 2 A/D converters per channel (ibaMS3xAI-1A/100A only) |
||
|
Resolution |
16 bit (18 bit internal) |
||
|
Filters |
|||
|
permanent in addition |
R/C low-pass, 1st order, 40 kHz Analog anti-aliasing filter (Butterworth), 4th order, 20 kHz Digital anti-aliasing filter (Chebyshev I)1, 8th order, cutoff frequency adjustable |
||
|
ibaMS3xAI-1A |
ibaMS3xAI-5A |
ibaMS3xAI-1A/100A |
|
|
Input signal range |
-3.0 A … +3.0 A |
-15.0 A … 15.0 A |
-6.25 A … +6.25 A -100 A … +100 A2 |
|
Max. input current |
±10.5 A |
±24 A |
±24 A (permanent) ±100 A (only for 1 s per minute) ±500 A (briefly for 0.2 s per 5 minutes)3 |
|
Measuring shunt |
25 mΩ |
5 mΩ |
2x 5.0 mΩ |
|
Input resistance |
|||
|
Device switched off |
25 mΩ |
5 mΩ |
2.5 mΩ |
|
Device switched on |
25 mΩ |
5 mΩ |
2.5 mΩ |
|
Input capacity |
n/a |
n/a |
n/a |
|
Sampling rate |
max. 40 kHz, freely adjustable |
||
|
Frequency range |
0 Hz to 20 kHz |
||
|
Accuracy |
< 0.1 % of total measuring range |
||
|
Electrical isolation |
|||
|
Channel-channel Channel - housing/power supply |
2.5 kV AC 2.5 kV AC |
||
|
Connector type inputs |
8-pin connector, clamp-type terminal (0.5 mm2 …10 mm2) and interlocking device, included in delivery, without jumper |
||