Each channel provides power frequency measurement.
Note |
|
|---|---|
|
In addition to the actual measured values, the power frequency signals are available as virtual signals in the signal tree and can be displayed, recorded and used for calculations like all other signals. For information on parametrization, see Power frequency [10Hz..80Hz] tab. |
|
Measuring properties
-
Frequency
Frequencies between 10 Hz and 80 Hz are supported.
-
Measuring interval
Measuring interval
Standard conformity
Accuracy
1 s
-
± 5 mHz
10 s
according to DIN EN 61000-4-30
± 0.5 mHz