The current of the channel load circuit has exceeded half of the current that is admissible for the protective function of the fuse. If a current is flowing that is too high, the IC switch switches off internally. The magnitude of the current depends on the number of impulses and the energy over time.
|
Protection class |
Description |
|---|---|
|
Permanent overcurrent protection |
Channel inactive at Iout min. >2,0 / typ. 2,3 / max. <2,7A |
|
Surge current protection |
Channel inactive at Iout * toc : e. g. Iout * toc -> 3Ax80ms / 5Ax33ms / 10Ax15ms / 20Ax7ms / 35Ax4ms (tolerance ±20%) toc = response time of the overcurrent protection |
|
Status signals |
|---|
|
DO_Err_OverCurrent_Ch[00…15] |