Analog outputs

ibaMS16xAO-10V

ibaMS16xAO-20mA

Number

16

Design

4 separated galvanically isolated roots of 4 outputs each

Resolution

16 bit

Filters

R/C low-pass 40 kHz

Output signal range

-10 V to +10 V

-20 mA to +20 mA

Load

≥ 1 kΩ

≤ 500 Ohm Ω

Output frequency

max. 40 kHz1

Delay

8 µs + 12 µs (setting time until 90 % of the output value is reached)

Accuracy

< 0.1 % of total measuring range

< 0.5 % of total measuring range

Electrical isolation

Root-root

2.5 kV AC

Root-housing/power supply

2.5 kV AC

Connector type

4x 12-pin multi-pin connector, screw-type terminal (0.14 mm2 to 1.5 mm2), included in delivery

Protective functions

Safe state

channel root switched off

Current limitation

short circuit protection

Hardware error (e. g. over temperature)

The root switches to „safe state“ (resettable via software).