Caution! |
|
|---|---|
|
You must only connect one conductor to each terminal connection. Several individual conductors, whether single-wired or fine-wired, are not permitted. Only connectors classified by iba may be used for connecting conductors. |
|
Connection technology power supply connector
|
Connection technology |
Push-in |
|||
|
Clamping range |
0.14 - 1.5 mm2 |
|||
|
Cable cross-section |
||||
|
Single wired |
0.14 - 1.5 mm2 |
|||
|
Fine wired |
0.14 - 1.5 mm2 |
|||
|
With wire end ferrule |
0.25 - 1.5 mm2 |
|||
|
With wire end ferrule/collar |
0.25 - 1.0 mm2 |
|||
|
Stripping length |
||||
|
Cross-section |
0.5 mm2 |
0.75 mm2 |
1.0 mm2 |
1.5 mm2 |
|
Single wired |
9 mm |
|||
|
Fine wired |
||||
|
With wire end ferrule |
10 mm |
|||
|
With wire end ferrule/collar |
12 mm |
- |
||
|
Recommended cables |
||||
|
Single wired |
H05V-U; H07V-U |
|||
|
Fine wired |
H05V-K; H07V-K |
|||
|
Screwdriver blade |
0.4 mm x 2.5 mm |
|||
|
Tightening torque connector |
0.3 Nm |
|||
Connection technology terminals for digital inputs/outputs
|
Connection technology |
Push-in |
|||
|
Clamping range |
0.13 - 1.5 mm2 |
|||
|
Cable cross-section |
||||
|
Single wired |
0.2 - 1.5 mm2 |
|||
|
Fine wired |
0.2 - 1.5 mm2 |
|||
|
With wire end ferrule |
0.25 - 1.5 mm2 |
|||
|
With wire end ferrule/collar |
0.25 - 0.75 mm2 |
|||
|
Stripping length |
||||
|
Cross-section |
0.25 mm2 |
0.5 mm2 |
0.75 mm2 |
1.5 mm2 |
|
Single wired |
8 mm |
|||
|
Fine wired |
||||
|
With wire end ferrule |
10 mm |
7 mm |
||
|
With wire end ferrule/collar |
10 mm |
- |
||
|
Recommended cables |
||||
|
Single wired |
H05V-U; H07V-U |
|||
|
Fine wired |
H05V-K; H07V-K |
|||
|
Screwdriver blade |
0.4 mm x 2.5 mm |
|||
Caution! |
|
|---|---|
|
Supply and measuring cables
|
|