How can gaps in the trend graph display be avoided?
Problem:
Gaps appear in the trend graph if the time base in ibaPDA is set too low for data acquisition.
However, the values are recorded correctly and without gaps in the DAT file or in the ibaHD-Server.
Remedy:
To obtain a complete display of the trend graph, the minimum size of the signal buffer must be increased in the client preferences (default 100,000). The maximum size is 100,000,000.
You can find the client preferences in the Configuration menu.