Danger! |
|
|---|---|
|
Electric shock If the device is used or operated in a manner other than specified in the Technical data chapter, the protection supported by the device may be impaired. |
|
|
Brief description |
|
|
Product name |
ibaM-COM |
|
Module label |
ibaM-COM |
|
Description |
Communication module for the ibaMAQS modular system |
|
Order number |
10.180010 |
|
Module-module interface |
|
|
Number |
1 |
|
Connection technology |
2x 8 sliding contacts |
|
Number of modules |
15 |
|
Data throughput |
|
|
General |
typically 512 Mbit/s; depends, among other things, on the time base in ibaPDA, the number of modules, and the signal selection or number of signals. |
|
Display |
capacity utilization display integrated in ibaPDA in % |
|
ibaNet interface |
|
|
Number |
2; switched |
|
Method |
copper |
|
ibaNet protocol |
ibaNet-E / ibaNet-E HP |
|
Connection technology |
2 RJ45 socket; 1GbE, Base-T |
|
Cable length (P2P) |
max. 100 m |
|
Cable type |
min. Cat. 6a, S/FTP |
|
Supply |
|
|
Power supply |
DC 24 V SELV; 4 A; external buffer module recommended |
|
Voltage range |
21.6 V ... 26.4 V DC |
|
Current consumption (max.) |
|
|
ibaM-COM |
0.18 A |
|
ibaM-COM with modules |
4 A |
|
Electrical isolation |
|
|
Supply – system |
none |
|
Connection technology |
3-pin header, 3.81 mm pitch |
|
Connector |
included in delivery; push-in, conductor max. 1.5 mm2, protected against reverse polarity, screw connection; information on conductor and stripping length see chapter Connection technology connector; order number 52.000031 |
|
Further interfaces, operating and indicating elements |
|
|
Indicators |
LEDs for operation and errors |
|
Operating and environmental conditions |
|
|
Temperature range |
|
|
Operation |
14 °F to 131 °F (-10 °C to +55 °C) |
|
Storage |
-13 °F to 185 °F (-25 °C to +85 °C) |
|
Mounting |
DIN rail according to EN 50022 (TS 35, DIN rail 35) |
|
Cooling |
passive |
|
Relative humidity |
15 % ... 95 % (indoor), no condensation |
|
Operating altitude |
0 m … 2000 m above sea level |
|
Protection type |
according to IP20; without test certificate according to IEC 60529 |
|
Certifications / standards |
CE, C-Tick, UKCA, FCC, IEC 61010-1, IEC 61000-6-5 Interface range 4 |
|
Pollution degree |
2 |
|
MTBF1 (+25 °C) |
5,102,664 hours / 582 years |
|
Dimensions |
|
|
Width x height x depth |
28 mm x 133 mm x 120 mm |
|
Height with open lever |
160 mm |
|
Height unit |
3 |
|
Installation clearances |
|
|
Top / bottom |
30 mm / 30 mm |
|
Left / right (system) |
10 mm / 10 mm |
|
Mounting position |
vertical, lever up |
|
Weight / incl. packaging |
0.25 kg / 0.55 kg |
|
Supplier's Declaration of Conformity 47 CFR § 2.1077 Compliance Information Unique Identifier: 10.180010, ibaM-COM Responsible Party - U.S. Contact Information iba America, LLC 370 Winkler Drive, Suite C Alpharetta, Georgia 30004 (770) 886-2318-102 www.iba-america.com FCC Compliance Statement This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. |