In the General tab, you can make basic settings and settings for the connection to the device.

Basic

Module Type (information only)

Indicates the type of the current module.

Locked

A module can be locked to avoid unintentional or unauthorized changing of the module settings.

Enabled

Enable the module to record signals.

Name

You can enter a name for the module here.

Comment

Extra description about the module. This will be displayed as tooltip in the signal tree.

Advanced

Watchdog

You can enable watchdog for attached modules.

If an error occurs on the I/O bus that would prevent data acquisition from continuing, this watchdog triggers immediately. This means that data acquisition is stopped and the modules are restarted. The acquisition of other modules continues in the meantime. If the error could be reset by restarting the I/O modules, data acquisition with the I/O modules will continue.

Only one attempt is made to reset the I/O bus. If the error persists after this, the system remains in error mode.

Configuration

Lock

This property determines if the configuration should be locked in the ibaNet-E device. When the configuration is locked, only the owner that sets the lock can change the configuration or remove the lock.

Connection

Auto enable/disable

When this option is enabled and ibaPDA cannot connect to this device during the start of the acquisition then it will disable this module and start the acquisition without it. During the acquisition it will try to reconnect to the device. When it succeeds it will automatically restart the acquisition with this module enabled.

If this option is not enabled then ibaPDA will not start the acquisition when it cannot connect to the device.

Data path

Select the transport protocol you want to use for data transfer between ibaPDA and the ibaNet-E device. The following are available:

  • MAC: Based on layer 2 of OSI model the communication runs without an IP address. It is used in pure ibaNet-E networks or non-routed networks. The data path MAC offers higher bandwidth with highly synchronous data.

    Enter the MAC address of the device in the field MAC address and select the appropriate network interface.

    Only with data path MAC, an ibaNet-E acquisition with High Performance (HP) is possible.

  • IPv4: Based on layer 4 of OSI model IP addresses are needed for UDP/IP communication. It must be used in routed networks.

    Enter the IP address of the device in the field IP address.

MAC address, Network interface

These fields appear when the data path MAC is selected.

IP Address

The field appears when the data path IPv4 is selected.

More functions

Read configuration from MCOM

Reads the most recently saved ibaPDA configuration from the device and adds it to the ibaPDA configuration. The ibaPDA module numbers cannot be read out. Therefore, new module numbers are created or free module numbers are assigned.

Modified settings are applied by clicking on <OK> or <Apply>.