Danger |
|
|---|---|
|
Electric shock The device is only designed for electrical measured variables as specified in the “Technical data” chapter! If the device is used or operated in a manner other than specified in the Technical data chapter, the protection supported by the device and the function itself may be impaired. This also applies to the permissible operating and environmental conditions. |
|
Danger! |
|
|---|---|
|
Permanent measuring voltage Permanent measuring voltages of up to 300 V DC will not destroy the device. Voltages of 300 V DC or higher may destroy the device and the device’s safety can no longer be guaranteed. |
|
Short description
|
Name |
ibaM-8DI-24V |
ibaM-8DI-220V |
|
Module label |
8DI-24V |
8DI-220V |
|
Description |
Input module with 8 digital channels for measuring voltage levels |
Input module with 8 digital channels for measuring voltage levels |
|
Order number |
10.181100 |
10.181110 |
Module-module interface
|
Number |
2 |
|
Connection technology |
4x 8 sliding contacts |
Digital inputs
|
Number |
8 |
|
|
Design |
galvanically isolated, single ended, protected against reverse polarity |
|
|
Sampling method |
parallel |
|
|
Level detection |
active |
|
|
Input signal typ. |
24 V DC |
220 V DC |
|
Signal level low/high |
||
|
log. 0 |
> -6 V; < +6 V |
> -56 V; < +56 V |
|
log. 1 |
< -10 V; > +10 V |
< -76 V; > +76 V |
|
Hysteresis |
3 V DC |
15 V DC |
|
Delay |
not relevant; excluded during data acquisition |
|
|
Input current |
typ. 1.1 mA DC |
|
|
ibaPDA timebase (update time) |
min. 10 µs; freely adjustable (integer multiple) |
|
|
Overvoltage category |
OVC III 300 V |
|
|
Debounce filter |
optional, 4 operating modes |
|
|
Electrical isolation |
||
|
Channel - channel |
basic insulation: OVC III 300 V |
|
|
Channel - system |
reinforced insulation: OVC III 300 V |
|
|
Connection technology |
2x 8-pin pin header, pitch 5 mm |
|
|
Connector |
2x enclosed; push-in, conductor max. 2.5 mm2, locking lever (latching), reverse polarity protection, lockable; For information on the conductor and stripping length, see chapter Connection technology connector ; Order number: 52.000054 |
|
Supply
|
Supply voltage |
24 V DC via module-module interface |
|
Current consumption (max.) |
|
|
Own consumption |
0.06 A |
|
Input/output current |
4 A |
Other interfaces, operating and indicating elements
|
Indicators |
LEDs for operation, channel states and errors |
Operating and environmental conditions
|
Temperature range |
|
|
Operation |
14 °F to 131 °F (-10 °C to +55 °C) |
|
Storage |
-13 °F to 185 °F (-25 °C to +85 °C) |
|
Mounting |
on DIN rail according to EN 50022 (TS 35, DIN rail 35) |
|
Cooling |
passive |
|
Relative humidity |
15 % … 95 % (indoor), no condensation |
|
Operating altitude |
0 … 2000 m above sea level |
|
Protection type |
according to IP20; without test certificate according to IEC 60529 |
|
Certifications / standards |
CE, C-Tick, UKCA, FCC, KC, IEC 61010-1, IEC 61000-6-5 interface range 4 |
|
Pollution degree |
2 |
|
Dimensions |
|
|
Width x height x depth |
28 mm x 133 mm x 120 mm |
|
Height with open lever |
160 mm |
|
Height unit |
3 |
|
Installation clearances |
|
|
Top / bottom |
30 mm / 30 mm |
|
Left / right (system) |
10 mm / 10 mm |
|
Installation position |
vertical, lever up |
|
Weight / incl. packaging |