Analog inputs
|
Number |
4 |
|
Design |
galvanically isolated, single ended; 3 pins per channel: voltage (U+) / GND (U-/I-) / current (I+) |
|
Input signal |
voltages up to 60 V ACpeak or 60 V DC; currents up to 20 mA ACpeak or 20 mA DC; switchable per channel |
|
Resolution |
24 bit (Delta-Sigma) |
|
ADC sampling rate |
100 kHz |
|
ibaPDA timebase (update time) |
min. 10 μs; freely adjustable (integer multiple); max. 1 ms for filter signals |
|
Filters |
|
|
ADC signal |
|
|
analog |
R/C low-pass, 1st order, 50 kHz |
|
digital |
Anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate |
|
Filter signal1 |
|
|
Like ADC signal, in addition: |
|
|
digital |
Anti-aliasing filter (Elliptic/Cauer); 10th order; cutoff frequency = 0.45 / timebase |
|
Measuring ranges |
|
|
Voltage (U) |
±2.5 V / ±10 V / ±24 V / ±60 V |
|
Current (I) |
±20 mA / 0…20 mA DC / 4…20 mA DC |
|
Input voltage max. |
|
|
Measurement category / CAT protection class (U) |
CAT III 100 V |
|
Current (I) |
1 V DC |
|
Input resistance |
|
|
Voltage (U) |
100 kΩ / 1 MΩ2; switchable |
|
Device switched off |
100 kΩ / 1.00 MΩ |
|
Device switched on |
115 kΩ / 1.02 MΩ |
|
Current (I) |
|
|
Device switched off |
50 Ω |
|
Device switched on |
50 Ω |
|
Input capacity |
|
|
Voltage (U) |
1.2 pF |
|
Current (I) |
n/a |
|
Accuracy (+25 °C) |
< 0.1 % of the respective double full scale value |
|
Electrical isolation |
|
|
Channel - channel |
Functional isolation: 2.5 kV AC |
|
Channel - system |
Functional isolation: 2.5 kV AC |
|
Connection technology |
2x 6-pin pin header, pitch 5.08 mm |
|
Connector |
2x enclosed; push-in, conductor max. 2.5 mm2, locking lever (latching), protected against reverse polarity, lockable; For information on the conductor and stripping length, see chapter Connection technology connector ; Order number: 52.000053 |
Status functions
|
Current measurement |
Overrange/underrange; reversed polarity; broken cable |
Additional functions
|
Power frequency measurement (10 Hz ... 80 Hz) |
Interval: 1 s / 10 s (according to IEC 61000-4-30) |