Analog inputs

Number

4

Design

galvanically isolated, single ended; 3 pins per channel: voltage (U+) / GND (U-/I-) / current (I+)

Input signal

voltages up to 60 V ACpeak or 60 V DC; currents up to 20 mA ACpeak or 20 mA DC; switchable per channel

Resolution

24 bit (Delta-Sigma)

ADC sampling rate

100 kHz

ibaPDA timebase (update time)

min. 10 μs; freely adjustable (integer multiple); max. 1 ms for filter signals

Filters

ADC signal

analog

R/C low-pass, 1st order, 50 kHz

digital

Anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate

Filter signal1

Like ADC signal, in addition:

digital

Anti-aliasing filter (Elliptic/Cauer); 10th order; cutoff frequency = 0.45 / timebase

Measuring ranges

Voltage (U)

±2.5 V / ±10 V / ±24 V / ±60 V

Current (I)

±20 mA / 0…20 mA DC / 4…20 mA DC

Input voltage max.

Measurement category / CAT protection class (U)

CAT III 100 V

Current (I)

1 V DC

Input resistance

Voltage (U)

100 kΩ / 1 MΩ2; switchable

Device switched off

100 kΩ / 1.00 MΩ

Device switched on

115 kΩ / 1.02 MΩ

Current (I)

Device switched off

50 Ω

Device switched on

50 Ω

Input capacity

Voltage (U)

1.2 pF

Current (I)

n/a

Accuracy (+25 °C)

< 0.1 % of the respective double full scale value

Electrical isolation

Channel - channel

Functional isolation: 2.5 kV AC

Channel - system

Functional isolation: 2.5 kV AC

Connection technology

2x 6-pin pin header, pitch 5.08 mm

Connector

2x enclosed; push-in, conductor max. 2.5 mm2, locking lever (latching), protected against reverse polarity, lockable; For information on the conductor and stripping length, see chapter Connection technology connector ; Order number: 52.000053

Status functions

Current measurement

Overrange/underrange; reversed polarity; broken cable

Additional functions

Power frequency measurement (10 Hz ... 80 Hz)

Interval: 1 s / 10 s (according to IEC 61000-4-30)