Analog inputs

Number

4

Design

galvanically isolated, single ended; additionally 2x GND and 2x GND with 50 Ω

Input signal

Voltages up to 24 V DC / IEPE sensors; switchable by channel

Input modes

24V DC / 24V AC / IEPE 0.1Hz / IEPE 1Hz; switchable by channel

IEPE 0.1Hz/1Hz

integrated constant current source: +4 mA (24 V DC)

Resolution

24 Bit (Delta-Sigma)

ADC sampling rate

100 kHz

ibaPDA timebase (update time)

min. 10 µs; freely adjustable (integer multiple); max. 1 ms1 in the case of filter signals

Filters

ADC signal

24V DC

Analog

R/C low-pass, 1st order, 50 kHz

Digital

anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate

24V AC

Analog

R/C low-pass, 1st order, 50 kHz R/C high-pass, 1st order, 1 Hz

Digital

anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate

IEPE 0.1Hz

Analog

R/C low-pass, 1st order, 50 kHz

Digital

R/C high-pass, 1st order, 0.1 Hz anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate

IEPE 1Hz

Analog

R/C low-pass, 1st order, 50 kHz

Digital

R/C high-pass, 1st order, 1 Hz anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x ADC sampling rate; oversampling = 32 x ADC sampling rate

Filter signal2

24V DC/AC / IEPE 0.1Hz/1Hz

Like ADC signal, in addition

Digital

anti-aliasing filter (Elliptic/Cauer), 10th order; cutoff frequency = 0.45 / timebase; or anti-aliasing filter (Butterworth), 2nd order; cutoff frequency = 0.45 / timebase; switchable

Measuring ranges

24V DC/AC

±24 V

IEPE 0.1Hz/1Hz

±10 V (at ~160 Hz and BIAS voltage ~12 V DC)

Input gain IEPE

none

Input resistance 24V DC/AC

Device switched off

1.0 MΩ

Device switched on

1.1 MΩ

Input capacity

107 pF

Accuracy (+25 °C)

24V DC

< 0.1 % of the double full scale value

24V AC

< 2 % of the double full scale value

IEPE 0.1Hz/1Hz

< 0.1 % of the double full scale value

Electrical isolation

Channel - channel

Functional isolation: 2.5 kV AC

Channel - system

Functional isolation: 2.5 kV AC

Connection technology

2x 6-pin pin header, pitch 5 mm

Connector

2x included in delivery; push-in, conductor max. 2.5 mm2, locking lever (latching), protected against reverse polarity, lockable; For information on the conductor and stripping length, see chapter Connector connection technology; Order number: 52.000052

Sensor cable length

The maximum length of the sensor cable depends on various factors, including the configured sampling rate. For the corresponding calculation formula, see chapter Connector connection technology.

Status functions

Input modes

24V DC/AC

Data valid

IEPE 0.1Hz/1Hz

Data valid, broken line, short circuit

Additional functions

Statistical values

Input modes

24V DC/AC / IEPE 0.1Hz/1Hz

Calculation basis

Interval

100 ms … 5000 ms, freely adjustable (in 1 ms steps)

Calculation

in blocks

Signal

ADC signal

Sampling

ADC sampling rate

General characteristic values

Characteristic values

Min, Max, Avg, Peak, Peak-to-Peak, RMS, Crestfactor, used range

Bandpass-filtered characteristic values

Number

6 bandpass filters per channel; each freely adjustable

Bandpass filter

Butterworth, 4th order

Bandwidth (min.)

50 Hz

Characteristic values

24V DC/AC

RMS, Peak-to-Peak, Crestfactor; can be integrated

IEPE 0.1Hz/1Hz

vRMS, vPeak-to-Peak, vCrestfactor or aRMS, aPeak-to-Peak, aCrestfactor; switchable

TEDS (according to IEEE-1451)

Design

0-wire

Supported EEPROMs

DS2430A, DS2431