The shield of a connected sensor should always be connected to the analog inputs of the ibaM-4AI-IEPE device and grounded on one side only. The stripped shield is connected as short as possible via a corresponding ground pin (GND) of the connectors.
The system must be grounded via the DIN rail.
Note |
|
|---|---|
|
The ibaM-4AI-IEPE device together with the system should not be positioned near drives and frequency converters. |
|