Modular concept
The I/O module described in this documentation is part of the ibaMAQS modular measurement system.
The modular system consists of a central unit (ibaM-DAQ processor module or the ibaM-COM communication module), which can be combined with up to 15 different I/O modules. Modules are available for discrete input and output signals as well as for special technological features.
The I/O modules do not require their own power supply since they are powered via the module-module interface. The operating status of the module as well as the status of the individual channels are indicated by LEDs.
ibaM-4AI-IEPE
The ibaM-4AI-IEPE module is designed for the acquisition of mechanical vibrations with IEPE vibration sensors. Different input modes can be set in ibaPDA for each channel for the analog inputs:
-
IEPE input with 1 Hz or 0.1 Hz high-pass filter
-
24 V AC input
-
24 V DC input
Overview of the most important features:
-
Input module with 4 analog inputs
-
Constant current source 4 mA for sensors
-
Typical for IEPE sensors
-
Detection of broken line and short circuit
-
Galvanically isolated analog inputs
-
24 bit resolution
-
Sampling rate A/D converter 100 kHz
-
Timebase 10 µs to 1 ms, freely adjustable
-
Analog and digital filters per channel
-
Rugged housing, easy installation
The maximum number of ibaM-4AI-IEPE modules on a processor or communication module is not limited. A maximum of 15 of these modules can be operated on one of the two central units.