Analog inputs

Number

4

Design

galvanically isolated, single ended

Input signal / nominal voltage

600 V AC

Resolution

24 bit (Delta-Sigma)

ADC sampling rate

500 kHz

Timebase ibaPDA (update time)

min. 2 μs; freely adjustable (integer multiple); max. 1 ms for filter signals

Filters

    ADC signal

analog

R/C low pass, 1st order, typ. 150 kHz

digital

anti-aliasing filter (FIR), 84th order; cutoff frequency = 0.45 x sampling rate ADC; oversampling = 32 x sampling rate ADC

    Filter signal1

            like ADC signal, in addition:

digital

anti-aliasing filter (Elliptic/Cauer) 10th order; cutoff frequency 0.45/timebase

Measuring ranges

±360 V / ±1700 V; switchable by channel

Measuring category

CAT III 600 V / CAT IV 300 V

Input impedance

Device switched on

2.0 MΩ

Device switched off

2.0 MΩ

Input capacity

50 pF

Accuracy (+25 °C)2

< 0,1 % of the respective double full scale value

Electrical isolation

Channel-channel

basic insulation: CAT III 600 V

Channel-system

reinforced insulation: CAT III 600 V

Connection technology

2x 4-pin pin header, pitch 7.62 mm

Connector

2x enclosed; push-in, conductor max. 2.5 mm2, locking lever (latching), reverse polarity protection, lockable; information on conductor and stripping length, see chapter Connection technology connector; order no. 52.000050

Additional functions

Phasor Measurement Unit3

integrated

Power frequency (10 Hz ... 80 Hz)

intervall 1 s / 10 s (according to IEC 61000-4-30)