The following table gives an overview of the available operation modes, link speed, number of signals, data sampling time and typical devices:

Protocol

Max. number of signals per FO link

Sampling time

Typical device

Single fiber input-only modes

2Mbit

32 INT + 32 Digital

≥1 ms

ibaPADU16/32 (old, S/N < 1000)

3Mbit

64 INT + 64 Digital

≥1 ms

ibaPADU8/16/32

64 REAL + 64 Digital

≥1 ms

ibaLink-SM-64-i-o

5Mbit

8 INT + 8 Digital

≥50 µs

SIMATIC TDC LO5

32Mbit

64 INT + 64 Digital

≥50 µs

SIMATIC TDC LO6

128 INT + 128 Digital

≥100 µs

SIMATIC TDC LO6

512 REAL + 512 Digital

≥800 µs

ABB AC 800PEC (1 ms)

DPM-S mode

≥800 µs

ibaBM-DPM-S (1 ms)

8 x (64 INT + 64 Digital)

≥1 ms

ibaBM-COL-8i-o (1 ms)

Bidirectional fiber modes (output link required)

5Mbit

8 INT + 8 Digital

≥40 µs

ibaPADU-8-M

ibaPADU-8-ICP

32Mbit Flex

variable*

≥10 µs

ibaPADU-S-CM

Single fiber output-only modes (output link required)

3Mbit

64 REAL + 64 Digital

≥1 ms

ibaNet750-BM

32Mbit

Not supported by PC software yet.

* Example: Payload transmission of 64 Byte at 25 µs sampling time or 3100 Byte at 1 ms.

Besides the mere hardware parameters the usability of board and devices in combination with a certain operational mode depends also on the iba software application.

Not all of iba application software products support all modes or cards at the time.

The following table shows the supported combinations of modes of operation and software applications:

Protocol

3Mbit

5Mbit

32Mbit

32Mbit Flex

Transmission rate

3.3 Mbit/s

5.0 Mbit/s

32 Mbit/s

32 Mbit/s

Sampling rate

1 Hz -1 kHz

0.5 kHz - 25 kHz

1.25 kHz - 20 kHz

0.5 kHz - 100 kHz

Number of signals per FO link

64 A + 64 D

8A + 8D

512 A + 512 D (1 ms) 64 A + 64 D (50 µs)

Up to 4060 bytes

Application

Input

Output

Input

Output

Input

Output

Input

Output

ibaPDA

1)

-

-

ibaLogic

-

-

-

-

= Ok, □ = possible, - = not supported

1) Alarm outputs (50 ms) via ibaFOB-4o-D, -io-D, -2io-D