Protocol |
Min. telegram cycle |
Max. signal sampling frequency |
Direction of communication x-directional |
Max. data volume (in bytes) |
Max. number of participants in the FO link |
---|---|---|---|---|---|
ibaNet 3Mbit |
1 ms |
1 kHz |
uni |
136 B (64 integer values, 64 binary values) |
8 (line topology) |
ibaNet 32Mbit 50µs |
50 µs |
20 kHz |
uni |
144 B (64 integer values, 64 binary values) |
1 |
ibaNet 32Mbit 100µs |
100 µs |
10 kHz |
uni |
288 B (128 integer values, 128 binary values) |
1 |
ibaNet 32Mbit Flex |
Min. 25 µs |
Max. 40 kHz |
bi |
64 B at 25 µs Tcycl 3113 B at 1 ms Tcycl |
15 (ring topology) |