Digital inputs

Number

2

Version

Electrically isolated, protected against polarity reversal, single ended

Input signal

24 V DC

Max. input voltage

±60 V permanent

Signal level log. 0

Signal level log. 1

> -6 V; < +6 V

< -10 V; > +10 V

Input current

1 mA, constant

Debounce filter

Optionally with 4 different operating modes, configurable in ibaPDA

Sampling rate

max. 40 kHz, freely adjustable

Delay

typ. 10 µs

Electrical isolation

Channel-channel

Channel-housing

2.5 kV AC

2.5 kV AC

Connection technology

Screw-type terminal (0.14 mm2 to 1.5 mm2), screw connection, included in delivery

Digital outputs

Number

2

Version

Galvanically isolated, solid-state DC switch

Switching voltage

max. 200 V DC, protection against surge voltages

Switching current

max. 350 mA (permanent), overcurrent protection

Switch delay

< 2 ms (at 100 mA)

ON resistance (log. 1)

max. 3.75 Ω (at 100 mA)

OFF resistance (log. 0)

min. 100 MΩ

Electrical isolation

Channel-channel

Channel-housing

2.5 kV AC

2.5 kV AC

Connection technology