Import
Import - Time range permissible
Defines the time interval in days in which new data can be read. Data that is older than this period is no longer read and is moved to the error folder. [Default: 100 days]
Bearing: Create additional trends in the spectrum
Specifies whether or not the “FFT level” is to be created. If this property is disabled, not all FFT levels for the bearing will be created. If the property is enabled, the “FFT level” is used in addition to the envelope curve level. Possible values: disabled, enabled [default: enabled]
Gear dam: Create additional trend in envelope spectrum
Specifies whether or not the “Gear damage levels” are to be created. If the property is disabled, the “Gear damage level” trend is not created when creating the gear. If the property is enabled, in addition to the “Gear mesh level” in the spectrum a “Gear damage level” is created in the envelope curve spectrum. Possible values: disabled, enabled [default: enabled]
File info key
Returns the names of the properties to be read from a DAT file and saved in the database. It is not mandatory for the property name to occur in every DAT file.
Channel info key
Returns the names of the properties to be read from a channel in a DAT file and saved in the database. The property name does not have to appear in every channel in the DAT file.
Disk
Receive e-mails
Enables e-mail notifications for disk monitoring.
Disk monitoring alarm threshold
Specifies the percentage limit for the alarm range which is used in the drive cleanup. Possible values: 85% - 95%
Disk monitoring warning threshold
Specifies the percentage limit for the warning range which is used in the drive cleanup. This value is calculated from the alarm threshold.
Warning threshold = Alarm threshold - 10%
Notification group
In the notification group, multiple trends can be combined into a single group. This notification group can then be used in the notification configuration in the user profile.
Depending on the selected level in the user profile, a notification is sent as soon as a trend from the group reaches or exceeds the set level.
Template
Under Templates you can create custom templates for the email notification.
Use the <+ Add> button to create a new template, which can then be modified.