Refer to the following table for the interface data for ibaBM- DP.

PROFIBUS interfaces

DP connectors

2 x 9-pin D-Sub connector (Bus0, Bus1)

Data transmission rate

9.6 kbit/s to 12 Mbit/s

DP slaves (can be configured as active slaves in the device)

max. 8, can be distributed as required on both PROFIBUS lines (can be extended on request)

Address range of the slaves

1 to 126

ibaNet interface

ibaNet protocols

Sampling cycle

Number of signals

32Mbit Flex

selectable beginning with 0.5 ms (1540 bytes), data amount depending on cycle time

up to 1024 analog values (BYTE, INT, WORD, DINT, DWORD, FLOAT, Big/Little Endian) + up to 1024 digital signals (bits)

a total max. of 4060 bytes at a cycle time of 1.4 ms

32Mbit (compatibility mode 1)

1 ms

Up to 512 analog values (BYTE, INT, WORD, DINT, DWORD, FLOAT, Big/Little Endian; max. 1984 bytes)

+ up to 512 digital signals (bits)

3Mbit (compatibility mode3)

1 ms

up to 64 analog values (INT or FLOAT)

+ up to 64 digital signals (bits)

Connection technology

2 ST connectors for RX and TX;

iba recommends the use of FO with multimode fibers of type 50/125 μm or 62.5/125 μm;

For information on cable length, see chap. Example for FO budget calculation.

Transmitting interface (TX)

Output power

50/125 µm FO cable

-19.8 dBm to -12.8 dBm

62.5/125 µm FO cable

-16 dBm to -9 dBm

100/140 µm FO cable

-12.5 dBm to -5.5 dBm

200 µm FO cable

-8.5 dBm to -1.5 dBm

Temperature range

-40 °F to 185 °F (-40 °C to 85 °C)

Light wavelength

850 nm

Receiving interface (RX)

Receiving sensibility2

100/140 µm FO cable

-33.2 dBm to -26.7 dBm

Temperature range

-40 °F to 185 °F (-40 °C to 85 °C)

Other interfaces

Ethernet

10/100 Mbit/s, RJ45 connector

Other interfaces

USB (only for service purposes)

Grounding screw