To use the mapping mode, set the rotary switches as follows: S1 = 7 and S2 = 0
If you want to use the mapping mode, you need an additional license (order data see chapter Order data).
The mapping mode provides extensive possibilities to exchange data between two PROFIBUS systems connected to Bus0 and Bus1 interfaces. A classic DP-DP coupler is available for transfer of output data of one slave to the input data range of an assigned slave in a bidirectional way. In addition the output data of existing slaves of the PROFIBUS system Bus0 can be sniffed and transferred to the input data range of an assigned slave. In total up to 8 of these mapping assignments can be used (when using the expansion of active slaves even 16).
For further information see chapter Mapping mode and chapter Mapping mode.