The figure shows the Settings page, when the device is set to compatibility mode 3Mbit (DP-64 mode).

In this mode, the device has to be configured via the web interface. The settings are made on the Settings page.

  1. The operating mode can be selected in the combo box DP-64-Mode.

    To open the selection list, click on the arrow in the box. The mode names correspond to those described in chapter Operating modes overview.



  2. Make sure that the two slaves are assigned to the correct bus line (bus 0 – connector X40, bus 1 – connector X41).

  3. Enter the slave address for each slave, as they are given in DP project engineering.

    The allowed address range reaches from 0 to 126.



  4. Use the <Submit> button to save the settings in the device.

  5. Use the <Refresh> button to refresh the settings display.