For measuring and recording data over ibaBM-DP in 32Mbit Flex mode, you need ibaPDA version 6.32.0 or higher.
For measuring and recording data over ibaBM-DP in compatibility mode 32Mbit, you need ibaPDA version 6.20.2 or higher.
For ibaPDA versions older than version 6.32.0, you can use the device module ibaBM-DPM-S. For further information on the ibaBM-DPM-S module, see the manual for "ibaBM-DPM-S" manual.
Caution |
|
|---|---|
|
When changing the slave configuration of the ibaBM-DP device (add, delete active slaves or transferring them on another bus) during operation, this results in a temporal decoupling of the slaves from the PROFIBUS. The communication to the DP master is interrupted. If the PLC (e .g. SIMATIC S7®) is not secured by OBs, this will result in a stop of the PLC! When changing addresses and data within slaves that have been already defined, there will be no disturbances in the PROFIBUS communication! |
|
Attention |
|
|---|---|
|
For preventing disturbances on the PROFIBUS, use for active slaves only free slave numbers that are not used by other devices! |
|