The operating modes (rotary switch S1) and the device address (rotary switch S2) are being set with the rotary switches.
|
S1 |
S2 |
ibaNet protocol |
Data volume / timebase |
Note |
|---|---|---|---|---|
|
Compatibility mode 3Mbit |
||||
|
0 |
0 |
3Mbit |
64A + 64D in 1 ms |
up to 2 slaves no sniffer function |
|
Compatibility mode 32Mbit |
||||
|
1 |
0 |
32Mbit |
512A + 512D in 1 ms Max. data volume of analog values: 1984 Bytes |
Sniffer function + up to 8 active slaves Redundancy mode* can be used |
|
32Mbit Flex mode** |
||||
|
1 |
1…F |
32Mbit Flex |
1024A + 1024D Max. data volume depends on timebase Max. possible data volume: 4060 Bytes at 1.4 ms timebase Min. timebase: 0.5 ms at max. possible data volume of 1540 Bytes |
Sniffer function + up to 8 active slaves Redundancy mode* can be used |
|
P2P mode |
||||
|
4 |
0 |
32Mbit |
||
|
Simulation mode* |
||||
|
5 |
0 |
Not used |
||
|
Mirror mode* |
||||
|
6 |
0 |
32Mbit |
See compatibility mode 32Mbit |
Sniffer function, no active slaves |
|
6 |
1...F |
32Mbit Flex |
See 32Mbit Flex mode |
Sniffer function, no active slaves |
|
Mapping mode* |
||||
|
7 |
0 |
Not used |
No data acquisition possible |
|
* additional license required
** default setting (with S2 = 1)
Note |
|
|---|---|
|
Compatibility mode 3Mbit/32Mbit In contrast to the predecessor,iibaBM-DP does not have any PROFIBUS terminating resistors and no switch for bridging the buses 0 and 1. Please use instead the terminating resistors on the PROFIBUS connectors. For connecting the buses 0 and 1, you may use a cable bridge. |
|