Description
The Siemens CP1626 module is the PCI Expression version of the CP1616 module and it must be installed in the ibaPDA computer in order to obtain this interface in the I/O Manager. The board is required for connecting to a Profinet communication network. Before this step, the board needs to be properly configured with SIMATIC system software (STEP 7, NetPro, etc.).
The module has the following properties:
-
2 PROFINET interface each with 2 ports
-
Connection with ibaPDA to port X1 (PROFINET controller)
-
PROFITNET must be configured so that CP1626, as the controller, reads the data from one or more PROFINET devices.
-
The CP1626 module only works if DMA is enabled.
Up to 4 CP1626 boards are supported per ibaPDA computer.
If the board has been setup correctly and connected to an active PROFINET network, the status bar shows the name of the controller (CP1626) and its status (online/offline). Extensive information regarding interrupts is available for diagnostic purposes.
A maximum of up to 1024 modules are supported per interface.
Note |
|
|---|---|
|
A different and more flexible PROFINET connection option is the use of the ibaBM-PN device in conjunction with an ibaFOB-io-D-card. |
|
Interface configuration
In principle, no settings are required at this stage. The following buttons are available:
-
<Reset>: resets the card.
-
<Open log file>: opens the PROFINET log file.
-
<Dump firmware trace buffer>: This button is used to issue the signal buffer of the firmware as a text file. ibaPDA can automatically detect CP1626 firmware errors. If such an error occurs, ibaPDA will output the firmware signal buffer automatically and record an error message in the event log.
-
<Reset counters>: Resets all diagnostic counters and copy times.
Connection table
The table gives an overview of all receivers configured on the board. With an established connection, the receiver has a green background. A red background shows that there is no connection.
Each row, i.e., each receiver address, corresponds to a module configured under this interface.
Available modules
-
PROFINETcontroller IRT top
-
PROFINET controller RT/IRT flex
-
Simotion D
Product name
ibaPDA-Interface-Profinet-CP (Art. no. 31.001350)
Other documentation |
|
|---|---|
|